Compare“ICM Controls ICM292A Direct Spark Ignition Furnace Control Board - Replacement for Rheem 62-24140-04” has been added to the compare list
ICM Controls ICM102 Delay on Make Timer with .03-10 Minute Adjustable Time Delay, Universal 18-240 VAC
In stock
Category: ICM Controls
ICM Controls ICM102 Delay on Make Timer with .03-10 Minute Adjustable Time Delay, Universal 18-240 VAC
Ideal for compressor staging and stagger starting multiple motors and other equipment. Helps to reduce power surges.
- Universal voltage operation
- Higher 1.5 amp power rating
- Knob-adjustable time delays
- Works with anticipator-type thermostats
- One model replaces many in field
- Ideal for compressor staging
- Simple 2-wire hookup
SPECIFICATIONS
- Voltage: 18-240 VAC
- 1.5 amps
- 15 amp inrush
- 40 mA holding current
- Frequency: 50/60 Hz
- Adjustable delay: .03-10 minutes (1.8-600 seconds)
- Voltage drop: 2.5 V @ 1.5 amps
- Dimensions: 2″ x 2″
REPLACES
- A-1: EAC-701-ADJ
- Diversified: AC-800
- Gemline: 1C310, 1C213
- Mars: 32019, 32391, 32367
- Supco: TD69
- Wagner/DiversiTech: ADM-1
MODE OF OPERATION
When power is applied to the input, the time delays begins. After the time delay is complete, the load energizes and remains energized as long as power is applied. The control is reset by removing power during or after the time delay period. The ICM102 provides thermostat interruption protection, even in the presence of a trickle current.
Installation Guide
Be the first to review “ICM Controls ICM102 Delay on Make Timer with .03-10 Minute Adjustable Time Delay, Universal 18-240 VAC”







Reviews
There are no reviews yet.